Electro Masters Corporation

Edmi MK6

Contact Now* Send an Inquiry to this supplier.
or
Start Order * Name your price

Quick Information

  • Model Number : Mk6 Genius Energy Meter

Description

 

Accuracy

• Class 0.5S (to IEC 60687)

• Class 1 & 2 (to IEC 61036)

Voltage

• Nominal - 57 to 240V (phase to neutral)

• Burden - < 10VA / phase at Vn (3 phase), as per IEC 62053-61, 1998

• Frequency 45-65 Hz

Current

• C.T. Range - 1/1.2A, 5/6A, 1/4A and 5/20A

• W.C. Range - 10/100A (Class 1 only)

• Short time over-current - 20 times the Imax for 0.5 seconds

• Burden - < 0.5VA/phase

Auxiliary Supply Options

• 240V, 110V (other voltages available on special order)

Measurement Modes

• Single phase (3 circuits)

• 3 phase 3 wire

• 3 phase 4 wire

Measured Energy Values

• 3 element, 4 quadrant

• Import/Export Wh, varh and VAh

• Absolute Wh, varh and VAh

• Phase A,B,C or Total

Other Measured and Displayed Values

• Power: W, var, VA

• True RMS Voltage (3 phase)

• True RMS Current (3 phase)

• Power factor

• Frequency

• Phasor angles

Pulsing Inputs / Outputs

• Maximum of 8 I/O with up to 8 outputs (2 standard) or 6 inputs

• Output voltage - 5 ~ 220V DC, 12 ~ 240V AC

• Output current - 0.1A maximum

• Output pulse width - 1ms to 250ms

• Programmable output polarity

• Input voltages - 5, 12, 48, 110, 240V AC/DC

• Time synchronized (optional)

Communications

• Local - ANSI type 2 optical or FLAGTM (IEC 1107)

• Remote - Isolated RS485 or RS232 or both

Communications Possibilities

• ANSI Type 2 Optical

• IEC 1107

• RS232 (RTS/CTS and DTR/DCD)

• RS485 (2 or 4 wire multidrop)

• SCADA

• Modems (PSTN/GPRS/GSM/CDMA)

• MV90TM

• MODBUS®

• PPP/GPRS

• DNP3

• Optional internal modem power supply

• Master/Slave arrangement with up to 31 ‘Slave’ meters accessed

through one ‘Master’ Gateway meter

Temperature Range

• Operating -10 to +60oC

• Storage -40 to +85oC

Time Keeping

• Accuracy (internal) +30 sec/month

• Backup time - 2 years without power

• Backup type - lithium battery and optional SuperCap

• Mains synchronized or internal crystal time keeping. Mains synchronized reverts to internal crystal on loss of all phase volts

Data Storage (Configuration, TOU Data and Load Survey)

• FlashRAM, indefinite storage period

• Battery backed up RAM

Time Of Use

• 8 rates plus unified rate

• Up to 12 separate import and export registers

• Up to 200 programmable special days

• Daily, Weekly, Monthly, Yearly, Special

• 13 or more previous periods

• Block or Rolling Maximum Demand

• Time of Maximum Demand

Load Survey / Profile

• NEM compliant

• 400 day-channel capacity at 30 minute intervals

• Up to 50 channels

• Interval programmable from 1 second to 1 month

• Multiple independent surveys

• Energy, instantaneous readings, pulsing inputs, average/min/max readings

Sag / Swell

• 5 cycle resolution

• Records time/date/phase/duration/worst excursion

• Programmable trigger levels

LCD Display

• 16 character by 2 line alphanumeric display

• Programmable units, multipliers and leading zeros

• Up to 64 user definable screen displays

• Displays any available meter parameter

Optional Functions

• Quality of supply (QOS) features

• Waveform capture

• Harmonic analysis to the 50th harmonic

• THD measurement

• Fundamental energy measurement

Equipment Failure Alarms (EFAs)

A single user defined alarm condition (via scripts) is available plus preprogrammed

alarms based on numerous:

• Self checks

• Tamper and wiring checks

These alarms can:

• Turn on an LED, LCD Indicator or relay output

• Record an event in the event log

• Trigger an event such as a remote alarm or dial an emergency number via scripts

Extensions for Customer Applications: standard or to order

The Genius meter introduces the concept of Extensions to the revenue metering world. The increasingly complex nature of revenue metering has necessitated the development of exciting new programming tools that allow customers to tailor the meter for specific applications. Using

“EziScript”, a scripting language developed by EDMI, complex register manipulations can be performed allowing sophisticated changes to the meter operation. EDMI offers custom Extension writing services. New Extensions are constantly under development - contact us to find out the latest updates

Examples of currently available Extensions are:

• Send SMS at percentage of maximum demand

• Average power factor for billing period

• LCD menu system

• Magnetic tamper detection

• Power factor control extension

• Maximum demand control of loads via pulsing outputs

• Average voltage, current, unbalance, THD etc

• Voltage sag / swell or power outage

• Power factor / power quality

• Voltage quality

• Send SMS on equipment failure alarm

Software

• EziView Windows software (optional), can be used for programming and reading the meter

• EziView also allows offline configuration of tariff programs and all meter parameters, for later upload


Product Image

Send an Inquiry to this supplier

Send an Inquiry to this supplier
* From
  To Efren G. Dacanay
Electro Masters Corporation
* Buying Product
- Please enter your specific buying item.
e.g. 42 inch LCD TV, leather executive chair
Category : Other Electrical Equipment
* Message

Use English only Max. 2000 characters. (Min. 20)

Send
EC21.com does not guarantee the validity of product information or the credentials of sellers.

Browse: Manufacturer Directory Premium Suppliers Site Map

About EC21 Contact Us Terms & Conditions Report Item Online Trading Risks Product Listing Policy

Copyright (c)1997-2026 EC21 Inc. All Rights Reserved. EC21 in KoreanChinese

Business Registry Number: 120-86-03931 | Mall order sales Registration Number: 강남-5838